7SR10, 7SR11, 7SR12 Applications Guide
© 2018 Siemens Protection Devices Limited
Chapter 7 Page 41 of 41
5.6.1 Broken Conductor example
Information recorded during commissioning:
I full load = 500A
I NPS = 50A
Therefore the ratio is given by 50/500 = 0.1
To allow for tolerances and load variation a setting of 200% of this value is recommended and
therefore the ratio for
46BC setting
should be set at 20%.
To allow for adequate time for short circuit fault clearance by time delayed protection the
46BC delay
should be set to 50seconds.
To ensure the broken conductor protection does not operate incorrectly during low load conditions,
where the three phases are less than 10% of normal load, the element should be inhibited by setting
the
46BC U/C Guarded
to Yes and selecting a
46BC U/C Guard Setting
to 0.1 x In
5.7 Circuit-Breaker Maintenance
The Relay provides Total, Delta and Frequent CB Operation Counters along with an I
2
t Counter to estimate the
amount of wear and tear experienced by a Circuit-Breaker. Alarm can be provided once set levels have been
exceeded.
Typically estimates obtained from previous circuit-breaker maintenance schedules or manufacturers data sheets
are used for setting these alarm levels. The relay instrumentation provides the current values of these counters.
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...