7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 52 of 52
3.7 81THD Total Harmonic Distortion Supervision
3.7.1 Reference
Parameter
Value
I
thd
Setting
5,6,.....100 %
t
d
Delay setting
0.02, 0.03…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
3.7.2 Operate and Reset Level
Attribute
Value
Ithd
op
Operate level
100 % Ithd,
±
5 % (Applied harmonic magnitude) or
±
1% Ithd
Operating range
0.2 to 20xI
n
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
Variation
-10 °C to +60 °C
≤
5 %
f
nom
± 5 %
≤
5 %
3.7.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
0 to 2xIthd: 55 ms,
±
15 ms
t
op
Operate time following delay
t
basic
+ t
d
,
±
1 % or
±
10 ms
Repeatability
±
1 % or
±
10 ms
Overshoot time
< 40 ms
Disengaging time
< 60 ms
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...