7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 43 of 52
Attribute
Value
t
op
Operate
time
char = IDMTL
[ ]
1
M
t
Vs
0
V
3
op
−
=
,
±
5 % or
±
65 ms
char = DTL
t
d
,
±
1 % or
±
40 ms
Reset Time
char = IDMTL
t
res
,
±
5 % or
±
65 ms
char = DTL
t
res
,
±
1 % or
±
40 ms
Repeatability
±
1 % or
±
20 ms
Overshoot time
< 40 ms
Disengaging time
< 100 ms