Chapter 4 - 7SR10 · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 77 of 78
Appendix 1
The operating mode of the device is set via the setting, or through a command sent to a communications port. There
are four options; Local, Remote, Local or Remote and Service.
The following table illustrates whether a function is Enabled (
✔
) or Disabled (
✖
) in each mode.
Operation Mode
Function
Local
Remote
Out of
Service
Control
Com1
✔
when Com1-Mode = Local
✔
when Com1-Mode = Remote
✖
Com2 (USB)
✔
when Com2-Mode = Local
✔
when Com2-Mode = Remote
✖
Fascia (Control Mode)
✔
✖
✖
Function Key (n)
✔
✔
when F Key(n) Mode = Remote
✖
Binary Input (n)
✔
when BI (n) Mode = Local
✔
when BI (n) Mode = Remote
✖
Binary Outputs
✔
✔
✖
Reporting
Spontaneous
IEC
✔
✔
✖
DNP3
✔
✔
✖
General Interrogation
IEC
✔
✔
✖
DNP3
✔
✔
✔
MODBUS
✔
✔
✔
Change Settings
Com1
✔
when Com1-Mode = Local
✔
when Com1-Mode = Remote
✔
Com2 (USB)
✔
when Com2-Mode = Local
✔
when Com2-Mode = Remote
✔
Fascia
✔
✔
✔
Historical Information
Waveform Records
✔
✔
✔
Event Records
✔
✔
✔
Fault Information
✔
✔
✔
Setting Information
✔
✔
✔
Fig. A1 Operating Mode Table
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...