7SR10, 7SR11, 7SR12 Applications Guide
© 2018 Siemens Protection Devices Limited
Chapter 7 Page 39 of 41
Scheme 3 (Comprehensive)
BI
+ve
-ve
BO
BI
+ve
-ve
TRIP COIL
52a
52b
-
Circuit
Breaker
TRIP CCT n FAIL
BO 1
BO n
Remote
Alarm
+
R
R
H7 Scheme Notes:
BI =19V DC (48V DC supply)
BI = 44V (110, 220V AC/DC supply)
BI = 88V (220V AC/DC supply)
R = 3K3 typical
Figure 5-8 Trip Circuit Supervision Scheme 3 (H7)
Scheme 3 provides full Trip supervision with the circuit breaker Open or Closed.
5.4.2 Close Circuit Supervision Connections
R
BI
+ve
-ve
+
BO 1
BO n
Remote
Alarm
BO
R
CLOSE
COIL
52a
52b
-
Circuit
Breaker
H5 Scheme Notes:
BI =19V DC (24, 48V DC supply)
BI = 44V, 88V (110, 220V AC/DC supply)
R = 3K3 typical
CLOSE CCT n FAIL
Figure 5-9 Close Circuit Supervision Scheme
Close circuit supervision with the circuit breaker Open or Closed.
NOTE:
To achieve higher isolation, in the dual TCS application, it is recommended to maintain one Binary Input channel
should not be connected between 110 V DC and 230 V AC control supply.
NOTE:
Use the correct threshold voltages for BI when using TCS with 2 BI.
NOTE:
It is recommended to use Resistor (R), when the low voltage BI is used in the high voltage application. For e.g:
BI44 is used 220 V DC application.
With use of Resistor(R) mentioned above, BI threshold will increase due to voltage drop across external resistor.
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...