7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 41 of 52
2.17 55 Power Factor
2.17.1 Reference
Parameter
Value
PF
s
55-n Setting
0.05…0.99
t
d
55-n Delay setting
0.00 … 14400 s
2.17.2 Operate and Reset Level
Attribute
Value
PF
op
Operate Level
PF
s
±
0.05
Reset Level
Under PF
≤
PF
op
+ 0.02
Over PF
≥
PF
op
- 0.02
Repeatability
±
0.05
Variation
-10 °C to +60 °C
±
0.05
f
nom
± 5 %
±
0.05
2.17.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
≤
80 ms
t
op
Operate time following delay
t
basic
+ t
d
,
±
1 % or
±
10 ms
Disengaging time
< 80 ms
2.17.4 Operate Threshold
Attribute
Value
Minimum levels for
operation
I
2.5 % I
n
V
2.5% V
n
P
0.01 Sn
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...