Chapter 4 - 7SR10 · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 39 of 78
5. DNP3 Definitions
5.1 Device Profile
The following table provides a “Device Profile Document” in the standard format defined in the DNP 3.0 Subset
Definitions Document. While it is referred to in the DNP 3.0 Subset Definitions as a “Document,” it is in fact a table, and
only a component of a total interoperability guide. The table, in combination with the Implementation Table provided
in Section 5.2 (beginning on page 42), and the Point List Tables provided in Section 5.3 (beginning on page
48), should provide a complete configuration/interoperability guide for communicating with a device implementing
the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library.
DNP V3.0
DEVICE PROFILE DOCUMENT
(Also see the DNP 3.0 Implementation Table in
, beginning on page 42).
Vendor Name: Siemens Protection Devices
Device Name: 7SR10, using the Triangle MicroWorks, Inc. DNP3 Slave Source Code Library, Version 3.
Highest DNP Level Supported:
For Requests:
Level 3
For Responses: Level 3
Device Function:
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28
(index) are supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or
01.
Output Event Object 11 is supported.
Maximum Data Link Frame Size (octets):
Transmitted:
256
Received:
256
Maximum Application Fragment Size (octets):
Transmitted:
2048
Received:
2048
Maximum Data Link Re-tries:
None
Fixed (3)
Configurable from 0 to 65535 (Default 3)
Maximum Application Layer Re-tries:
None
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable as: Never, Only for multi-frame messages, or Always
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes
Configurable as: “Only when reporting event data”, or “When reporting event data or multi-fragment
messages.”
Timeouts while waiting for:
Data Link Confirm:
None
Fixed at ____
Variable
Configurable (2sec)
Complete Appl. Fragment:
None
Fixed at ____
Variable
Configurable
Application Confirm:
None
Fixed at ____
Variable
Configurable (10sec)
Complete Appl. Response:
None
Fixed at ____
Variable
Configurable
Others:
Transmission Delay, (Configurable, default 0 sec)
Select/Operate Arm Timeout, (Configurable, default 5 sec)
Need Time Interval, (Configurable, default 30 minutes)
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...