background image

ELR-19N

Earth Leakage Relay 

FEATURE

TECNICAL SPECIFICATION

MECHANICAL DIMENSION

KEY OPERATION

Earth Leakage Current Monitoring In 1Ø - 2W, 3Ø-3W 
And 3Ø-4W                                                                          

System 

Test Mode Available.

Auto/Manual Triping Reset Facility.

Test/Trip Reset Via Front Key 

Input Current  

Display Currant Range

Resolution  

30 mA To 3.00 Amp AC 

0.030 To 3.000 Amp AC

INPUT SPECIFICATION :

 

If Current in mA   =  1 mA
If Current in Amp = 0.001A

Display

 

Keys

 

Upper: 4 Digit ,7 Seg., 0.56”, Red
Lower: 4 Digit ,7 Seg., 0.56”,Green

SET, INC, DEC, ENT/RST

Relay

Relay Type

Rating 

1 Nos.

1 C/O (NO-C-NC)

10A,230V AC Resistive Load

AUXILIARY SUPPLY :

Supply Voltage

100 To 250 V AC

Power Consumption
(VA Rating) 

4VA @ 230 VAC MAX

DISPLAY & KEYS :

 

OUTPUT SPECIFICATION :

 

TERMINAL CONNECTION

OPERATION MODE

For 2 sec

For 5 sec

PARAMETER SETTING MODE

FUNCTION

KEY PRESS

To Enter in Parameter Setting

To Enter in Test Mode

To Reset the Relay Contact 
Manually After Tripping

Page -1

96

52

92

92

3

96

Outline Dimension (mm)

Panel Cutout 
Dimension (mm)

R

Earth Leakage Relay

ENT

RST

SET

ELR 19N

Set Value (A)

Ampere

TEST

0

0

0

2

1

9

8

4

ENVIRONMENT CONDITION:

Relative Humidity

Protection Level

(As per request)

 Operating Temp.

0°C to 55°C

UP to 95% RH 
(non-condensing)

IP-65 (Front side) As per IS/IEC
60529 : 2001

Made in India

www.multispanindia.com

1

2

3

4

7

8

9

12

13

14

10

11

5

16

17

18

19

20

6

15

NC

C

NO

L

N

S1

S2

CBCT

L1

L2

L3

N

TO

LOAD

 

100-250V AC 

50/60Hz,  4VA

!

ENT

RST

TEST

SET

To set parameter value

To increment parameter value.

To decrement parameter value.

Set parameter to be save & exit. 

SET

TEST

ENT

RST

Read complete instructions prior to installation 
and operation of the unit. 

WARNING :

 Risk of electric shock.

SAFETY PRECAUTION

!

       All safety related codifications, symbols and instructions that 
appear in this operating manual or on the equipment must be 
strictly followed to ensure the safety of the operating personnel 
as well as the instrument. 

      If all the equipment is not handled in a manner specified by
 the manufacturer, it might impair the protection provided by the 
equipment.

MAINTENANCE

1. The equipment should be cleaned regularly to avoid blockage 
    of ventilating parts.         

2. Clean the equipment with a clean soft cloth. Do not use 
    isopropyl alcohol or any other cleaning agent.

3. Fusible resistor must not be replaced by operator. 

WARNING GUIDELINES

WARNING : Risk of electric shock.

 1. To prevent the risk of electric shock, power supply to the 
    equipment must be kept OFF while doing the wiring 
     arrangement. Do not touch the terminals while power is 
     being supplied.  

 2. To reduce electro magnetic interference, use wire with 
    adequate rating and twists of the same of equal size shall 
     be made with shortest connection.            

 3. Cable used for connection to power source, must have a 
     cross section of 1mm or greater. These wires should have 
     insulations capacity made of at least 1.5kV.      

 4. When extending the thermocouple lead wires, always use
     thermocouple compensation wires for wiring for the RTD
     type, use a wiring material with a small lead resistance
     (5    max per line) and no resistance differentials among 
     three wires should be present.    

 5. A better anti-noise effect can be expected by using 
     standard power supply cable for the instrument.         

Ω

INSTALLATION GUIDELINES

1. This equipment, being built-in-type, normally becomes a 
    part of main control panel and in such case the terminals
    do not remain accessible to the end user after installation 
    and internal wiring.  

2. Do not allow pieces of metal, wire clippings, or fine metallic 
    fillings from installation to enter the product or else it may 
    lead to a safety hazard that may in turn endanger life or 
    cause electrical shock to the operator.      

3. Circuit  breaker or mains switch must be installed between 
    power source and supply terminal to facilitate power ‘ON’ 
    or ‘OFF’ function. However this mains switch or circuit 
    breaker must be installed at convenient place normally 
    accessible to the operator.     

4. Use and store the instrument within the specified ambient 
    temperature and humidity ranges as mentioned in this 
    manual.     

MECHANICAL INSTALLATION GUIDELINES

1. Prepare the panel cutout with proper dimensions as shown 
    above.

   

2. Fit the unit into the panel with the help of clamp given.

   

3. The equipment in its installed state must not come in close 
    proximity to any heating source, caustic vapors, oil steam, 
    or other unwanted process Byproducts.
   

4. Use the specified size of crimp terminal (M3.5 screws) to 
    wire the terminal block. Tightening the screws on the 
    terminal block using the tightening torque of the range of 
    1.2 N.m.

   

5. Do not connect anything to unused terminals. 
   

Input :30 mA To 3.00 Amp AC

Dimension:

size (mm)

Panel cutout

96(H) x 96(w) x 52(D)

96(H) x 96(w) x 52(D)

Size (mm)

 

Panel Cutout

96(H) X 96(W) X 52(D)

92(H) X 92(W)

DIMENSION :

 