![Siemens 7SR10 Argus Series Скачать руководство пользователя страница 147](http://html.mh-extra.com/html/siemens/7sr10-argus-series/7sr10-argus-series_manual_383097147.webp)
7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 49 of 52
3.3 60CTS & 60CTS-I Current Transformer Supervision
3.3.1 Reference
Parameter
Value
I
thresh
Current Threshold
0.05, 0.1… 2xI
n
I
Applied Current
(for operate time)
Healthy CT
Phases
5 x I
thresh
Failed CT phase 0
t
d
Delay setting
0.3, 20.00, 20.50… 100, 101…
1000, 1010… 10000, 10100…
14400 s
Directional Relays have additional VT settings
V
thresh
Voltage Threshold
7, 8… 110 V
3.3.2 Current & Voltage Threshold
Attribute
Value
I
op
CT failed current level
100 % I
thresh
,
±
5 % or
±
1% I
n
Reset level
90 % I
op,
±
5 % or
±
1% I
n
V
op
CT failed voltage level
100 % V
thresh
,
±
2 % or
±
0.5 V
Reset level
110 % V
op
,
±
2 % or
±
0.5 V
Repeatability
±
1 %
Variation
-10 °C to +60 °C
≤
5 %
f
nom
± 5 %
harmonics to f
cutoff
≤
5 %
3.3.3 Operate and Reset Time
Attribute
Value
t
basic
Basic operate time
50 ms
±
20 ms
Operate time
t
d
+ t
basic
,
±
1 % or
±
20 ms
Repeatability
±
1 % or
±
20 ms
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...