7SR10 Technical Manual
Chapter 4 - Page 46 of 78
© 2018 Siemens Protection Devices
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
32
0
Analog Change Event
- Any Variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
32
1
32Bit-Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
2
16Bit-Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
3
32Bit-Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
4 (default -
see note 1)
16Bit-Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
5
short floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
6
long floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
7
short floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
8
long floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
33
0
Frozen Analog Event
- Any Variation
33
1
32-Bit Frozen Analog Event
(without Time)
33
2
16-Bit Frozen Analog Event
(without Time)
33
3
32-Bit Frozen Analog Event
(with Time)
33
4
16-Bit Frozen Analog Event
(with Time)
33
5
Short Floating Point
Frozen Analog Event
33
6
Long Floating Point
Frozen Analog Event
33
7
Extended Floating Point
Frozen Analog Event
34
0
Analog Input Deadband
(Variation 0 is used to
request default variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
34
1
16 bit Analog
Input Deadband
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
34
2 (default -
see note 1)
32 bit Analog
Input Deadband
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34
3
Short Floating Point
Analog Input Deadband
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...