Chapter 4 - 7SR10 · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 65 of 78
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
192 Freq Last Trip
0,3
5
7
1.000
1.000
196 Frequency Max
0,3
2
4
100.000
1.000
197 S 3P Max
0,3
2
4
10.000
1000000.000
294 Ia THD
0,3
2
4
100.000
0.100
295 Ib THD
0,3
2
4
100.000
0.100
296 Ic THD
0,3
2
4
100.000
0.100
330 CB Trip Time Meter
0,3
2
4
1000.000
0.010
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name
Range/Options
Default
Setting
Notes
Unsolicited
Mode
DISABLED, ENABLED
DISABLED
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Destination
Address
0 - 65534
0
As Required
Setting is only
visible when DNP3
Unsolicited Events
set to Enabled.
DNP3
Application
Timeout
5, 6 ... 299, 300
10s
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...