7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 46 of 52
2.21 81 Under/over frequency
2.21.1 Reference
Parameter
Value
Fs
Setting
43, 43.01… 68 Hz
V
s
Guard
Guard Setting
35, 35.5, …199.5, 200 V
Hyst
Hysteresis setting
0, 0.1… 2 %
td
Delay setting
0.00, 0.01… 20.0, 20.1… 100.0, 101.…1000, 1010 … 10000 ,
10100 … 14400 s
2.21.2 Operate and Reset Level
Attribute
Value
F
op
Operate level
100 % F
s
,
±
10 mHz
Reset level
overfrequency
(100 % - hyst) xF
op,
±
10 mHz
underfrequency
(100 % + hyst) xF
op,
±
10 mHz
Repeatability
±
1 %
Variation
-10 °C to +60 °C
≤
5 %
2.21.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic
operate time
(for ROCOF
between 0.1
and 5.0 Hz/sec)
overfrequency
Typically
<
150 ms
Maximum
<
190 ms
underfrequency
Typically
<
150 ms
Maximum
<
190 ms
t
op
Operate time following delay
t
basic
+ t
d
,
±
1 % or
±
10 ms
Repeatability
±
1 % or
±
10 ms
Disengaging time
<
140 ms
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...