7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 21 of 52
2.6 47 Negative Phase Sequence Voltage
2.6.1 Reference (47)
Parameter
Value
Vs
Setting
1, 1.5… 90 V
V
s
Guard
Guard Setting
1, 1.5, …199.5, 200 V
Hyst.
Hysteresis
0, 0.1… 80 %
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010… 10000,
10100… 14400 s
2.6.2 Operate and Reset Level (47)
Attribute
Value
V
op
Operate level
100 % Vs,
±
2 % or
±
0.5 V
Reset level
(100%-Hyst.) x V
op
± 1 % or ± 0.25 V
Repeatability
±
1 %
Variation
-10 °C to +60 °C
≤
5 %
f
nom
± 5 %
≤
5 %
2.6.3 Operate and Reset Time (47)
Attribute
Value
t
basic
Element basic operate time
0 V to 2.0xVs, 80 ms,
±
20 ms
0 V to 10xVs, 55 ms,
±
20 ms
t
op
Operate time following delay
t
basic
+ t
d
,
±
2 % or
±
20 ms
Repeatability
±
1 % or
±
20 ms
Overshoot time
< 40 ms
Disengaging time
< 100 ms
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...