7SR10 Description of Operation
©2018 Siemens Protection Devices Limited Chapter 1 Page 71 of 77
Setting name
Range
Default
Setting
Notes
COM1-RS485 Parity
NONE, ODD, EVEN
EVEN
As Required
The parity set on all of
the relays connected to
the same RS485 bus
must be the same and
in accordance with the
master device.
COM1-RS485 Mode
Local, Remote, Local Or
Remote
Remote
Remote
Selects whether the
port is Local or Remote.
Unsolicited Mode
DISABLED ENABLED
DISABLED
As Required
Setting is only visible
when COM1 Protocol is
set to DNP3
Destination
Address
0 … 65534
0
As Required
Setting is only visible
when COM1 Protocol is
set to DNP3
To Control
System
B
Term
A
GND
1
2
3
4
RS 485
Screened
twisted pair
Rear terminals
RS 485
Screened
twisted pair
Rear terminals
Ext Wire loop to
include line
terminating Res
1
2
3
4
Figure 6-6 Communication to Multiple Devices from Control System using RS485
6.2 CB Maintenance
6.2.1 Output Matrix Test
The feature is only visible from the Relay fascia and allows the user to operate the relays functions. The test of
the function will automatically operate any Binary Inputs or LED’s already assigned to that function.
Any protection function which is enabled in the setting menu will appear in the Output Matrix Test.
6.2.2 CB Counters
The following CB maintenance counters are provided:
CB Total Trip Count:
Increments on each trip command issued.
CB Total Trip Manual Open
Selects whether the CB Total Trip Counter is incremented for
Manual Open Operations. If disabled, the CB Total Counter
will only increment for protection trip commands.
CB Delta Trip Count:
Additional counter which can be reset independently of the
Total Trip Counter. This can be used, for example, for
recording trip operations between visits to a substation.
CB Delta Trip Manual Open
Selects whether the CB Delta Trip Counter is incremented for
Manual Open Operations. If disabled, the CB Delta Trip
Counter will only increment for protection trip commands.
CB Count to AR Block: (Only in Auto-reclose Displays the number of CB trips experienced by the CB
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...