7SR10 Description of Operation
©2018 Siemens Protection Devices Limited Chapter 1 Page 25 of 77
Section 3: Protection Functions
3.1 Current Protection: Phase Overcurrent (67, 51, 50)
All phase overcurrent elements have a common setting for the 50 elements and 51 elements to measure either
fundamental frequency RMS or True RMS current:
True RMS current:
50 Measurement
= RMS,
51 Measurement
= RMS
Fundamental Frequency RMS current:
50 Measurement
= Fundamental,
51 Measurement
=
Fundamental
3.1.1 Directional Control of Overcurrent Protection (67)
The directional element produces forward and reverse outputs for use with overcurrent elements. These outputs
can then be mapped as controls to each shaped and instantaneous over-current element.
If a protection element is set as non-directional then it will operate independently of the output of the directional
detector. However, if a protection element is programmed for forward directional mode then operation will occur
only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for
reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically
the forward direction is defined as being ‘away’ from the busbar or towards the protected zone.
The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the
directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it.
The reverse operate zone is the mirror image of the forward zone.
Voltage polarisation is achieved for the phase-fault elements using the quadrature voltage i.e. at unity power
factor I leads V by 90°. Each phase current is compared to the voltage between the other two phases i.e for
normal phase sequence 1-2-3:
I
L1
~ V
23
I
L2
~ V
31
I
L3
~ V
12
When the device is applied to reverse sequence networks, i.e. 1-3-2, the polarizing is corrected internally by the
Gn Phase
Rotation setting in the
CT/VT Config menu.
The characteristic angle can be user programmed to any angle between -95
°
and +95
°
using the
67 Char Angle
setting. The voltage is the reference phasor (Vref) and the
67 Char Angle
setting is added to this to adjust the
forward and reverse zones.
The centre of the forward zone is set by (Vref Angle +
67 Char Angle
) and should be set to correspond with Ifault
Angle for maximum sensitivity i.e.
For fault current of -60° (I lagging V by 60°) a
67 Char Angle
of
+30°
is required for maximum sensitivity
(i.e. due to quadrature connection 90° - 60° = 30°).
OR
For fault current of -45° (I lagging V by 45°) a
67 Char Angle
of
+45°
is required for maximum sensitivity
(i.e. due to quadrature connection 90° - 45° = 45°).
Two-out-of-three Gate
When the
67 2-Out-Of-3 Logic
setting is set to
Enabled
, the directional elements will only operate for the
majority direction, e.g. if I
L1
and I
L3
are detected as forward flowing currents and I
L2
is detected as reverse current
flow, phases L
1
and L
3
will operate forwards, while phase L
2
will be inhibited.
Minimum Polarising Voltage
The
67 Minimum Voltage
setting defines the minimum polarising voltage level. Where the measured polarising
voltage is below this level no directional control signal is given and operation of protection elements set as
directional will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise
voltages can be present.
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...