Parameterizing Steps
05.2003
6SE7087-6JP60
Siemens AG
9-8
Operating Instructions
SIMOVERT MASTERDRIVES
P114 = ?
WARNING!
INCORRECT SETTINGS CAN BE DANGEROUS!
For vector control only:
Process-related boundary conditions for control
0: Standard drives
(default)
1: Torsion, gear play
2: Acceleration drives
3: Load surge
4: Smooth running characteristics
5: Efficiency optimization
6: Heavy-duty starting
7: Dynamic torque response in field-weakening range
See "Drive setting" section for description
P100=1,2
Thermal motor
protection desired?
System with motor protection according to UL regulation?
The motor temperature is calculated via the motor current.
(In the pre-setting, motor overload protection in accordance with
UL regulation is activated!)
no
yes
P382 = ?
P383 = ?
Specify motor cooling
0: self-ventilated
1: forced-ventilated
(automatically pre-set for P095 = 2, P097 > 0)
Enter the thermal time constant of the motor in s
automatically pre-set for P095 = 2, P097 > 0
The motor load limit (P384.2) is pre-assigned to 100 %.
P383 = 0
P095=2
P097>0
P700.1 = ?
Select setpoint and command source
(sheet s1...s4, s6, s71, s72, s82, s83)
0: PMU + MOP
1: Analog and digital inputs on the terminal strip
2: Fixed setpoints and digital inputs on the terminal strip
3: MOP and digital inputs on the terminal strip
4: USS1 (e.g. with SIMATIC)
5: not used
6: PROFIBUS (CBP) (without fig.)
7: OP1S and fixed setpoints via SCom2
8: OP1S and MOP via SCom2 (X103: PMU)
P368 = ?
Enter the USS bus address
P918.1 = ?
Enter the PROFIBUS address
P368 = 0,1,2,3
4,7,8
6
P370 = 1
Start of quick parameterization
0: No parameter change
1: Parameter change in acordance with selected combination
of parameter modules
(automatic factory setting according to P366)
(followed by automatic parameterization as for
P115 = 1)
P060 = 0
Return to the user menu
End of quick parameterization