Maintenance
05.2003
6SE7087-6JP60
Siemens AG
10-2
Operating Instructions
SIMOVERT MASTERDRIVES
10.1.1
Replacing the fan in units up to 45 mm wide
To replace the fan, the inverter has to be disconnected from the supply
and removed.
After removing the X20 connector which is protected against polarity
reversal and undoing the two cover screws, unscrew the fan and
withdraw the connector.
Fit the fan in the reverse order, making sure that the arrow indicating
the direction of air flow points to the inside of the unit.
Make sure that the leads to the fan are connected the right way round.
Otherwise the fan will not operate!
10.1.2
Replacing the fan in units up to 90 mm wide
To replace the fan, the inverter has to be disconnected from the supply
and removed.
After removing the X20 connector which is protected against polarity
reversal and unscrewing the two cover screws, the fan can be
dismantled by pushing out the internals of the insert rivets and the
connector can be disconnected. The insert rivets can be re-used.
Fit the fan in the reverse order, making sure that the arrow indicating
the direction of air flow points to the inside of the unit.
Make sure that the leads to the fan are connected the right way round.
Otherwise the fan will not operate!
Removal
DANGER
Installation
DANGER
Removal
DANGER
Installation
DANGER