05.2003
Parameterizing Steps
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
Operating Instructions
9-7
For v/f control (0..2) a linear curve is set in P330 (P330 = 1:
parabolic).
The pulse encoder has a pulse number of P151 = 1024 per
revolution.
The following inputs of motor data are necessary if the motor
deviates from the converter data, if one of the vector control
types (P100 = 3, 4, 5) has been selected or if speed feedback is
used (P100 = 0). In the case of motor outputs higher than
approx. 200 kW one of the vector control types should be used.
Enter the open/closed-loop control type (sheet r0 to r5)
0: v/f open-loop c n-controller with pulse encoder
(P130 = 11)
1: v/f open-loop control
2: v/f open-loop control, textile
3: Vector control without tachometer (f-control)
4: Vector control with tachometer (n-speed)
with pulse encoder (P130 = 11)
5: Torque control (M control)
with pulse controller (P130 = 11)
P100 = ?
P095=2
P097>0
P101 = ?
Enter the rated motor voltage in V
as per rating plate
P102 = ?
Enter the rated motor current in A
as per rating plate
(group drives: total of all motor currents)
P104=?
IEC motor: Cos (phi)
as per rating plate
NEMA motor: nominal rating [Hp]
(group drives: total of all ratings)
P105=?
NEMA motor: Enter the motor efficiency in %
as per rating plate
P106=?
P107 = ?
Enter the rated motor frequency in Hz
as per rating plate
P108 = ?
Enter the rated motor speed in rpm
as per rating plate
P109 = ?
Enter the motor pole pair number
(is automatically calculated)