Connecting-up
05.2003
6SE7087-6JP60
Siemens AG
7-16
Operating Instructions
SIMOVERT MASTERDRIVES
♦
10 V auxiliary voltage (max. 5 mA) for supplying external
potentiometers
♦
Analog output, suitable for use as current or voltage output
♦
1 analog input, suitable for use as current or voltage input
♦
1 additional digital input
♦
1 floating NO contact
Terminal
Designation
Meaning
Range
13
P10 V
+ 10 V supply for ext.
potentiometers
+ 10 V
±
1.3 %
Imax = 5 mA
14
N10 V
−−−−
10 V supply for ext.
potentiometers
−−−−
10 V
±
1.3 %
Imax = 5 mA
15
AO2
Analog output 2
10 bit + sign
Voltage:
16
M AO2
Ground for analog output 2
±
10 V / Imax = 5 mA
Current:
0...20 mA R
≤
500
Ω
17
AI2
Analog input 2
11 bit + sign
Voltage:
18
M AI2
Ground for analog input 2
±
10 V / Ri = 60 k
Ω
Current:
Rin = 250
Ω
19
DI7
Digital input 7
24 V, 10 mA
20
HS1
NO contact
DC 30 V / max. 0.5 A
21
HS2
(floating)
Minimum load 7 mA
Connectable cross-section: 0.14 mm
2
to 1.5 mm
2
(AWG 16)
Table 7-17
Control terminal strip X102