05.2003
Connecting-up
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
Operating Instructions
7-15
The following connections are provided on the control terminal strip:
♦
4 combined digital inputs and outputs
♦
2 additional digital inputs
♦
1 analog input
♦
1 analog output
♦
24 V auxiliary voltage supply (max. 60 mA, output only!) for the
inputs.
If the digital inputs are supplied by an external 24 V voltage supply, it
must be referred to ground terminal X101.2. Terminal X101.1 (P24
AUX)
must not
be connected to the external 24 V supply.
Terminal
Designation
Meaning
Range
1
P24 AUX
Aux. voltage supply
DC 24 V / 60 mA
2
M24 AUX
Reference potential
0 V
3
DIO1
Digital input/output 1
24 V, 10 mA / 20 mA
4
DIO2
Digital input/output 2
24 V, 10 mA / 20 mA
5
DIO3
Digital input/output 3
24 V, 10 mA / 20 mA
6
DIO4
Digital input/output 4
24 V, 10 mA / 20 mA
7
DI5
Digital input 5
24 V, 10 mA
8
DI6
Digital input 6
24 V, 10 mA
9
AI
++++
Analog input
++++
11 bit + sign
differential input:
10
AI
−−−−
Analog input
−−−−
± 10 V / Ri = 40 k
Ω
11
AO
Analog output
10 bit + sign
± 10 V / 5 mA
12
M AO
Ground analog output
Connectable cross-section: 0.14 mm² to 1.5 mm² (AWG 16)
Terminal 1 is at the top when installed.
Table 7-16
Control terminal strip
In the case of digital inputs, levels below 3 V are interpreted as low and
levels above 13 V as high.
X101 - Control
terminal strip
WARNING