Faults and Alarms
10.2001
6SE7087-6JP60
Siemens AG
13-8
Operating Instructions
SIMOVERT MASTERDRIVES
Number / Fault
Cause
Counter-measure
F060
MLFB is missing
This is set if the MLFB = 0 after exiting
INITIALIZATION (0.0 kW). MLFB = order
number.
After acknowledgement, in INITIALIZATION
enter a suitable MLFB in parameter P070
MLFB (6SE70..). (Only possible with the
corresponding access stages to both access
parameters).
F061
Incorrect
parameterization
A parameter entered during drive setting (e.g.
P107 Mot Rtd Freq, P108 Mot Rtd Speed,
P340 Pulse Frequency) is not in a permissible
range (depending on control type)
Acknowledge the fault and change the
corresponding parameter value. The missing
parameter is indicated in r949 as a fault value.
F062
Multi-parallel circuit
not Compact PLUS
Fault in connection with the multi-parallel
circuit or board ImP1 has been detected.
r949 = 10:
Communications card does not reply. When
writing the control word, BUSY is not active if
CSOUT is inactive. Communications card is
probably not inserted.
R949 = 11,12:
Timeout during BUSY during initialization.
BUSY does not become active within 1 sec.
R949 = 15:
Timeout during BUSY during normal
communication. BUSY does not become
active within 1 sec.
R949 = 18:
Timeout when reading out the fault information
from the ImPIs. Within one second after
activation of FAULT no fault cause can be
supplied by the IMP1.
R949 = 20+i:
HW conflict. This is set if bit HWCONF is set in
status word of slave i. (Fault in the
configuration of the multi-parallel circuit)
r949 = 30+i:
HW version of ImPI isnot compatible. The
relevant slave number is contained in i.
R949 = 40:
Number of slaves does not tally with the
setpoint number of slaves of the unit.
R949 = 50+i
Inconsistency in the number of slaves. The
number of slaves notified by the ImPI is not in
conformance with the number of status words
or with the setpoint number of slaves of the
MLFB.
Counter-measure:
- Check ImPI or communications card and
replace, if necessary.
- Check configuration of multi-parallel circuit.
- Check parameterization.
-
Replace CU
- Replace ImPI.