10.2001
Faults and Alarms
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
Operating Instructions
13-17
Number / Fault
Cause
Counter-measure
F145
Technology board fault
not Compact PLUS
See TB documentation
F146
Technology board fault
not Compact PLUS
See TB documentation
F147
Technology board fault
not Compact PLUS
See TB documentation
F148
Fault 1
Function blocks
An active signal is present at binector U061
(1).
Examine cause of fault, see function diagram
710
F149
Fault 2
Function blocks
An active signal is present at binector U062
(1).
Examine cause of fault, see function diagram
710
F150
Fault 3
Function blocks
An active signal is present at binector U063
(1).
Examine cause of fault, see function diagram
710
F151
Fault 4
Function blocks
An active signal is present at binector U064
(1).
Examine cause of fault, see function diagram
710
F152
Signs of life repeatedly
invalid.
After an appropriate number of invalid signs of
life, the sign of life monitoring block has gone
into fault status.
Check cause of fault, see function diagram
170
F243
Link int.
Fault in internal linking. One of the two linked
partners does not reply.
Replace CU (-A10), or replace the unit
(Compact PLUS)
F244
ParaLink int.
Fault in the internal parameter linking
Release comparison of gating unit software
and operating software regarding the transfer
parameters.
Replace CU (-A10), or replace the unit
(Compact PLUS)
F255
Fault in EEPROM
A fault has occurred in the EEPROM.
Switch off the unit and switch it on again. If the
fault re-occurs, replace CU, or replace the unit
(Compact PLUS)
Table 13-1
Fault numbers, causes and their counter-measures