Technical Data
05.2003
6SE7087-6JP60
Siemens AG
12-6
Operating Instructions
SIMOVERT MASTERDRIVES
Thermal overload of the external braking resistor must be avoided by
appropriate configuration. If necessary, the converter can be switched
off by a thermoswitch which monitors the temperature of the external
braking resistor (see Fig. 12-1).
SIMOVERT MASTERDRIVES
VC Compact PLUS
-X6
G
-X6
H
-X101.1
Y
ϑ
Thermo-
switch
ext.
braking
resistor
HS2
HS1
.21
-X102.20
Main
contactor
Y = Binary input which activates the fault trip of the converter,
e.g. -X101.7 (binary input 5)
-X1
Parameterization for the possible binary inputs Y:
Terminal
Binary input
Parameterization
-101.3
1
P586 = 10
.4
2
P586 = 12
.5
3
P586 = 14
.6
4
P586 = 16
.7
5
P586 = 18
.8
6
P586 = 20
-102.19
7
P586 = 22
Fig. 12-1
Converter with external braking resistor and fault trip via
thermoswitch