05.2003
Connecting-up
Siemens AG
6SE7087-6JP60
SIMOVERT MASTERDRIVES
Operating Instructions
7-13
Bidirectional
digital inputs
and outputs
I
out
≤
20 mA
X101
5V
24V
In
Out
Out
In
Out/In
In
Out
In
Out
In
Out
In
Out
In
4 bidirectional digital inputs/outputs
Outputs
Reference voltage
P10 V / N10 V
I
≤
5 mA
Aux. power
supply
60 mA
5V
24V
In
5V
24V
2
1
3
4
5
6
7
8
19
10
11
12
Micro-
controller
P5V
BOOT
R
S232 T
x
D
Digital inputs
Ri = 3.4 k
Ω
1
2
3
4
5
6
7
8
9
R
S232 R
x
D
PMU
X103
13
14
P10
N10
Slot B
Slot A
BOOT
n.
c
.
15
16
D
A
D
A
In
5V
24V
1
2
17
18
D
A
S3
4 5
-10...+10 V
D
A
-10...+10 V
M
M
X102
In
In
A
S
I
C
30
29
28
27
26
25
24
23
Track A
Track B
Tacho M
zero
Control
Tacho P24
Mottemp BS
Mottemp
X104
Pulse
encoder
I
≤
190 mA
Motor
temperature
sensor
KTY84 or
PTC thermistor
AI 1
AI 2
Analog input 2
(non-floating)
11 bit + sign
U: R
in
= 60 k
Ω
I: R
in
= 250
Ω
=
(close S3)
10 bit + sign
U: I
≤
5 mA
AO 2
AO 1
Analog output 2
Analog output 1
R
S485P.
9
Inputs
21
20
HS1
HS2
Digital input
Ri = 3.4 k
Ω
Analog input 1
(non-floating)
11 bit + sign
R
in
= 60 k
Ω
Serial interface 2
(RS485)
24 V output
Serial interface 1
(RS232)
Floating contact switch
30 V / 0.5 A
Out
10 bit + sign
U: I
≤
5 mA
I: 0...+20 mA
0...+20 mA
3
S4
R
S485N
.
External 24 V
supply
OFF
ON
Bus terminating resistor
P24 AUX
M24
RS485N
RS485P
UART
35
36
P24V
M24
34
33
X9
1
2
+
24 V
ext.
-
int. 24 V-SNT
NTC
X100
Controller
F1*)
*) Type of fuse -F1: Miniature circuit-breaker 6 A characteristic C
e. g. Siemens 5SX2 106-7 (see attached sheet)
Fig. 7-4
Overview of the standard connections