Technical Data
05.2003
6SE7087-6JP60
Siemens AG
12-8
Operating Instructions
SIMOVERT MASTERDRIVES
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 45 °C is calculated as
follows:
Total derating = Derating
altitude
x Derating
ambient temperature
K = K
1
x K
2
It must be borne in mind that total derating must
not be greater
than 1!
Example: Altitude:
3000
m
K
1
= 0.845
Ambient temperature: 35 °C
K
2
= 1.25
→
Total derating = 0.845 x 1.25 = 1.056 (= 1)
3Ph 380..480V 37,4A
50/60Hz Zmin=1%
3Ph 0-380..480V 0-500Hz
34A
54,4A (30 s)
6SE7023-4EP60-Z
Z=K80
6SE7023-4EP60
F2N62047500032
Year of manufacture
Month of manufacture
Unit designation
Fig. 12-3
Rating plate
The date of manufacture can be derived as follows:
Character
Year of manufacture:
Character
Month of manufacture
N
P
R
S
2001
2002
2003
2004
1 to 9
O
N
D
January to September
October
November
December
Table 12-4
Assignment of characters to the month and year of manufacture