Faults and Alarms
10.2001
6SE7087-6JP60
Siemens AG
13-10
Operating Instructions
SIMOVERT MASTERDRIVES
Number / Fault
Cause
Counter-measure
F079
SCB telegram failure
not Compact PLUS
No telegram has been received by the SCB
(USS, peer-to-peer, SCI) within the telegram
failure time.
- Check the connections of the SCB1(2).
- Check P704.03"SCom/SCB Tlg OFF"
- Replce SCB1(2)
- Replace CU (-A10)
F080
TB/CB initialization
fault
Fault during initialization of the board at the
DPR interface
Fault value r949:
1: Board code incorrect
2: TB/CB board not compatible
3: CB board not compatible
5: Error in configuration data
6: Initialization timeout
7: TB/CB board double
10: Channel error
Check the T300/CB board for correct
contacting, check the PSU power supply,
check the CU / CB / T boards and check the
CB initialization parameters:
- P918.01 CB Bus Address,
- P711.01 to P721.01 CB parameters 1 to 11
F081
OptBrdHeartbeat-
Counter
Heartbeat-counter of the optional board is no
longer being processed
Fault value r949:
0: TB/CB heatbeat-counter
1: SCB heartbeat-counter
2: Additional CB heartbeat-counter
- Acknowledge the fault (whereby automatic
reset is carried out)
- If the fault re-occurs, replace the board
concerned (see fault value)
- Replace ADB
- Check the connection between the subrack
and the optional boards (LBA) and replace, if
necessary
F082
TB/CB telegram failure
No new process data have been received by
the TB or the CB within the telegram failure
time.
Fault value r949:
1 = TB/CB
2 = additional CB
- Check the connection to TB/CB
- Check P722 (CB/TB TlgOFF)
- Replace CB or TB
F085
Add. CB initialization
fault
A fault has occurred during initialization of the
CB board.
Fault value r949:
1: Board code incorrect
2: TB/CB board not compatible
3: CB board not compatible
5: Error in configuration data
6: Initialization timeout
7: TB/CB board double
10: Channel error
Check the T300 / CB board for correct
contacting and check the CB initialization
parameters:
- P918.02 CB Bus Address,
- P711.02 to P721.02 CB Parameters 1 to 11
F087
SIMOLINK initialization
fault
A fault has occurred during initialization of the
SLB board.
- Replace CU, or replace the unit (Compact
PLUS)
- Replace SLB
F090
Mld Param.
An error occurred when attempting to change
a parameter from the standstill measurement
or the rotating measurement (Mot ID).
Power down and power up again. If it
reoccurs, replace CU, or replace the unit
(Compact PLUS)