Connecting-up
05.2003
6SE7087-6JP60
Siemens AG
7-6
Operating Instructions
SIMOVERT MASTERDRIVES
The DC link bus module serves as the electrical connection of the
individual units on the DC link side. It is of significance if further
inverters also have to be fed.
Bar
Designation
Meaning
Range
3
PE3
Protective conductor connection
2
D / L-
DC link voltage -
DC 510 - 650 V
1
C / L+
DC link v
DC 510 - 650 V
Connectable cross-section: "Electro-plated copper" 3x10 mm, rounded
off according to DIN 46433 (EN 13601)
Bar 1 is at the front when installed.
Table 7-2
DC link bus module
The motor connection is located at the lower section of the unit.
Terminal
Meaning
Range
PE2
Protective conductor connection
U2
Phase U2 / T1
3 AC 0 V - 480 V
V2
Phase V2 / T2
3 AC 0 V - 480 V
W2
Phase W2 / T3
3 AC 0 V - 480 V
Connectable cross-section: 4 mm
²
(AWG 10)
Terminal PE2 is at the front when installed.
Table 7-3
Motor connection
The connector has to be screwed firmly to the housing (providing
resistance to vibration and protecting against being inadvertently
withdrawn).
The motor cables must be dimensioned in accordance with VDE 298,
Part 2.
After installation of the connector, the shield of the motor cable must be
fixed to the shield plate through a large surface area.
X3 - DC link bus
module
X2 – Motor
connection
U2
PE2
V
2
W
2