First Start-up
10.2001
6SE7087-6JP60
Siemens AG
3-2
Operating Instructions
SIMOVERT MASTERDRIVES
If the PMU does not show status °009 after completion
of the unit initialization, or if the unit has already been
parameterized before, you should carry out a parameter
reset to factory setting.
If necessary, carry out
parameter reset to
factory setting
See section
"Parameterization"
AAA
Parameterizing by
download or with
parameter modules
See section
"Parameterization"
After checking the unit and the cabling once more,
power up the line voltage or DC bus voltage, if you have
not already done so, and perform a function test
according to your parameterization.
Function test
siehe
"Anschließen"
und "EMV-
gerechter
Aufbau"
It must be ensured that no danger for
persons and equipment can occur by
energizing the power and the unit. It is
recommended not to couple the driven
machine until the function test has
been successfully completed.
WARNING
Further start-up and parameterization according to
your specific requirements
siehe "Ans