Name
Description
[MF2 Service] Level
Warning
The output switches when the signal attenuation value reaches the criti‐
cal value, for example due to contamination.
Options
•
off
•
on
Factory setting
•
on
[MF2 Service] Temp.
Warning
The output switches when the interior device temperature reaches the
critical value.
Options
•
off
•
on
Factory setting
•
on
[MF2 Service] Plausib.
Warning
The output switches if extrapolated measured values are to be output for
implausible measured values
ErrRej
.
This may be caused by an internal error, hardware errors, obstruction of
the light beam, optical interference or electrical interference.
Options
•
off
•
on
Factory setting
•
on
[MF2 Service] Not
Ready
The output switches when the device is not ready for operation. Possible
causes could be hardware errors, optical or electrical interference or
a deactivated laser diode. This warning message is also issued during
initialization.
Options
•
off
•
on
Factory setting
•
on
[MF2 Service] Heating
Status
The output switches if the internal device heater is in operation.
Options
•
off
•
on
Factory setting
•
on
10.3.11
Module 22:
Setup Preset Static
Type
Configuration module, no input and output data
Description
This module is used to set the reference value for the static preset via digital input MF1
see "MF1 – Preset submenu", page 43
NOTE
If module 5
Distance/i2w, Preset Dyn./o2w
is also loaded, the static preset value is
overwritten by the dynamic preset value from the input data of module 5.