Input values
Rel. Adr.
Description
0
Current distance in the selected resolution taking into account the offset
and measuring direction.
Type
•
Signed 16-bit number in two´s complement
Module parameters
Name
Description
Distance Resolution
Select the resolution for the distance output value via the digital data
interface. The output value corresponds to the measured value [mm]
divided by the selected resolution. The parameter does not have any
influence on the measured value shown on the display.
If
free Distance Resolution
is selected, the associated value can be set in
module 26
Free Distance Resolution
.
Options
•
0.1 mm
•
0.125 mm
•
1 mm
•
10 mm
•
100 mm
•
free Distance Resolution
Factory setting
•
0.1 mm
10.3.3
Module 3:
Speed/i2w
Type
Input module, 2 words, consistent
Description
This module reads the currently determined speed.
NOTE
If there was no valid measured value due to a device fault, a missing reflector or
contamination, then the value
0
is output for the speed and the corresponding bits are
set in the status bytes.
Input values
Rel. Adr.
Description
0
Current speed in the selected resolution taking into account the direction
of measurement.
Type
•
Signed 32-bit number in two´s complement
PROFIBUS INTERFACE
10
8014755/19H8/2021-10-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP
61
Subject to change without notice