6.4.4
PROFIBUS OUT connection diagram
+5 V
A
B
1
2
4
grn
red
GND
3
nc
5
1
1
not connected
1
4
3
5
2
Table 8: PROFIBUS OUT connection, female connector, M12, 5-pin, B-coded
Contact
Signs
Wire color
Description
1
+5 V
–
Bus v5 V, electrically isolated for
terminator
2
A
Green
Data signal -
3
GND
–
Bus voltage 0 V, electrically isolated for ter‐
minator
4
B
red
Data
5
nc
–
–
6.4.5
Terminator
NOTE
PROFIBUS terminators are available as accessories,
The bus is terminated by an active terminator at the beginning and end of each PROFI‐
BUS segment. The two terminators always have to be supplied with 5V bus voltage via
the respective devices to ensure fault-free operation.
The external terminator is connected directly to the PROFIBUS OUT connection
"PROFIBUS OUT connection diagram", page 34
on the distance sensor.
6
ELECTRICAL INSTALLATION
34
O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFIBUS DP
8014755/19H8/2021-10-15 | SICK