20
Setting the user travel units
Assembler – Introduction
Example B: Incre-
ments
• Travel distance factor NUMERATOR = 1
• Travel distance factor DENOMINATOR = 1
Example C: Out-
put revolutions
• Travel distance factor NUMERATOR = Increments/motor revolution × gear ratio i =
4096 × 4 = 16384
• Travel distance factor DENOMINATOR = 1
Practical informa-
tion
Practical information for determining the travel distance factor during startup.
e.g. setting the user travel units in mm.
1. Set both the travel distance factors NUMERATOR and DENOMINATOR to the value
1 (
→
user travel units = increments).
2. Optional number of user travel units (increments), e.g. 100 000 increments.
3. Measure the covered distance in point 2 of the plant e.g.:
• Starting position = 1000 mm
• Target position = 1453 mm
• Distance covered
= 453 mm
4. Enter the travel distance factors in the program header of the Assembler:
• Travel distance factor NUMERATOR = 100 000
• Travel distance factor DENOMINATOR = 453
20.1.2 UNIT
All travel distance entries are displayed with a unit in the program window.
This unit can be entered in the program header for UNIT. It can be up to five characters
in length.