Manual – IPOSplus®
295
22
Binary inputs/outputs
Assembler – Programming
Setting several
outputs
It is possible to set several binary outputs at the same time, e.g. to output a binary coded
table position number. This is done by writing the decimal value of the table position
number to system variables H480 or H481.
Example
Output table position number 11 via DIO11 ("11" requires 3 outputs; that is, outputs
DO10, DO11 und DO13):
SET H480 = 11
All binary outputs are reset by setting the system variables H480 and H481 to "0".
This only makes sense if all outputs are set as IPOS
plus®
outputs. Outputs with other
parameter settings are written by the firmware and should not be modified.
SET H480 = 0 Reset the outputs of option DIO11 or DIP11
SET H481 = 0 Reset the outputs of the basic unit
Table 5: Assigning system variable H480/H481 to binary output terminals