U.2.44
SEL-421 Relay
User’s Guide
Date Code 20090715
Installation
Connection
Figure 2.40
Control Output OUT108
Program OUT108 to respond to NOT HALARM by entering the following
SEL
OGIC®
control equation with a communications terminal, with
AC
SEL
ERATOR
QuickSet:
OUT108 :=
NOT HALARM
When the relay is operating normally, the NOT HALARM signal is at
logical 1 and the b contacts of control output OUT108 are open.
When a status warning condition occurs, the relay pulses the NOT HALARM
signal to logical 0 and the b contacts of OUT108 close momentarily to
indicate an alarm condition.
For a status failure, the relay disables all control outputs and the OUT108 b
contacts close to trigger an alarm. Also, when relay power is off, the OUT108
b contacts close to generate a power-off alarm. See
for information on relay self-tests.
The relay pulses the SALARM Relay Word bit for software programmed
conditions; these conditions include settings changes, access level changes,
and alarming after three unsuccessful password entry attempts.
The SEL-421 also pulses the BADPASS Relay Word bit after three
unsuccessful password entry attempts.
You can add the software alarm SALARM to the alarm output by entering the
following SEL
OGIC
control equation:
OUT108 :=
NOT (HALARM OR SALARM)
Tripping and Closing Outputs
To assign the control outputs for tripping and closing, see
Tripping and Closing on page U.4.62
. In addition, you can use the
SET O
command (see
for more details). You can also use the
front panel to set and verify operation of the outputs (see
).
N/O
N/C
C
OUT108
OUT108
a
b
(connect alarm here)
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...