U.6.17
Date Code 20090715
User’s Guide
SEL-421 Relay
Testing and Troubleshooting
Test Methods
Step 6. View the target status change.
a. Increase the current source to produce a current
magnitude greater than 10.00 A secondary in the relay.
b. Observe the 50P1 target on the front-panel display.
You will see the 50P1 element status change to 1 when
the input current exceeds the 50P1P setting threshold.
Step 7. Press
{ESC}
to return to the
MAIN MENU
.
View Relay Elements With a Front-Panel LED
The procedure in the following steps shows you how to use a front-panel LED
to view a change-in-state for the 50P1 Phase Instantaneous Overcurrent
element. Use the factory defaults for the pickup level (see
). For more
information on the 50P elements, see
Instantaneous Line Overcurrent
.
In this example, use
AC
SEL
ERATOR
QuickSet to configure the relay. You must
have a computer that is communicating with the SEL-421 and running the
AC
SEL
ERATOR
QuickSet (see
Making Settings Changes: Initial Global
In addition, you need a variable current source
suitable for relay testing.
Step 1. Prepare to control the relay with
AC
SEL
ERATOR
QuickSet by
establishing communication, checking passwords, and reading
relay settings (see
Making Settings Changes: Initial Global
)
.
Step 2. Set a pushbutton LED SEL
OGIC
control equation.
a. Expand the
Front Panel
branch of the
Settings
tree
view and click
Pushbuttons
(see
).
AC
SEL
ERATOR
QuickSet displays the
Pushbuttons
.
b. Click in the
PB4_LED
text box and type
50P1
.
c. Tab or click to any other text box.
AC
SEL
ERATOR
QuickSet checks the validity of the
setting.
Figure 6.9
Setting Pushbutton LED Response:
AC
SEL
ERATOR
QuickSet
Step 3. Click
File > Save
to save the new settings in
AC
SEL
ERATOR
QuickSet.
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...