U.1.13
Date Code 20090715
User’s Guide
SEL-421 Relay
Introduction and Specifications
Specifications
Specifications
U.User’s Guide
General
AC Current Inputs (Secondary Circuits)
Note:
Current transformers are Measurement Category II.
5 A nominal:
15 A continuous,
linear to 100 A symmetrical
500 A for 1 second
1250 A for 1 cycle
Burden:
0.27 VA @ 5 A
2.51 VA @ 15 A
1 A nominal:
3 A continuous,
linear to 20 A symmetrical
100 A for 1 second
250 A for 1 cycle
Burden:
0.13 VA @ 1 A
1.31 VA @ 3 A
AC Voltage Inputs
300 V
L-N
continuous (connect any voltage up to 300 Vac)
600 Vac for 10 seconds
Burden:
0.03 VA @ 67 V
0.06 VA @ 120 V
0.8 VA @ 300 V
Power Supply
125/250 Vdc or 120/230 Vac
Range:
85–300 Vdc < 35 W or 85–264 Vac
Nominal Frequency:
50/60 Hz
Range:
30–120 Hz
Burden:
<120 VA
48/125 Vdc or 120 Vac
Range:
38–140 Vdc < 35W or 85–140 Vac
Nominal Frequency:
50/60 Hz
Range:
30–120 Hz
Burden:
<120 VA
24/48 Vdc
Range:
18–60 Vdc
Burden:
<35 W
Control Outputs
Standard
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1s Rating:
50 A
MOV Protection
(maximum voltage):
250 Vac/330 Vdc
Pickup/Dropout Time:
6 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10000 operations):
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
Cyclic Capacity (2.5 cycle/second):
48 Vdc
0.50 A
L/R = 40 ms
125 Vdc
0.30 A
L/R = 40 ms
250 Vdc
0.20 A
L/R = 40 ms
Note:
EA certified relays do not have MOV protected standard
output contacts.
Hybrid (high current interrupting):
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1s Rating:
50 A
MOV Protection
(maximum voltage):
330 Vdc
Pickup/Dropout Time:
6 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10000 operations):
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle
for thermal dissipation):
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Note:
Do not use hybrid control outputs to switch ac control
signals. These outputs are polarity dependent.
Fast Hybrid (high-speed high current interrupting):
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating:
50 A
MOV Protection
(maximum voltage):
250 Vac/330 Vdc
Pickup Time:
10
μ
s, resistive load
Dropout Time:
8 ms, resistive load
Update Rate:
1/8 cycle
Break Capacity (10000 operations):
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle
for thermal dissipation):
48 Vdc
10.0 A
L/R = 40 ms
125 Vdc
10.0 A
L/R = 40 ms
250 Vdc
10.0 A
L/R = 20 ms
Note:
Per IEC 60255-23:1994, using the simplified method of
assessment.
Note:
Make rating per IEEE C37.90-1989.
Auxiliary Trip/Close Pushbuttons (Select Models Only)
Resistive DC or AC Outputs with Arc Suppression Disabled:
Make:
30 A
Carry:
6 A continuous carry
1 s Rating:
50 A
MOV Protection:
250 Vac/330 Vdc/130 J
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...