U.5.35
Date Code 20090715
User’s Guide
SEL-421 Relay
Front-Panel Operations
Front-Panel Automatic Messages
For alarm point assertions, qualified event reports (including trip events), and
status warnings, the relay displays the corresponding full-screen automatic
message, only if the front-panel display is in the time-out or standby condition
(the relay is scrolling through the default display points/enabled metering
screens of the
ROTATING DISPLAY
or is displaying the
MAIN MENU
). When a
status warning, alarm, or event is triggered, the relay full-screen presentation
is similar to the screens of
.
Figure 5.41
Sample Status Warning, Alarm Point Assertion, and Trip EVENT SUMMARY Screens
If you are on site using the SEL-421 front panel in menus and screens other
than the
MAIN MENU
and a status warning occurs, alarm point asserts, or an
event report triggers, the relay shows automatic messages at the bottom of the
active screen in the message area.
For example, the message area shows
RELAY STATUS WARNING
for a status
warning.
is an example of a status warning notification that
appears in the message area of a
LOCAL CONTROL
(local bit) screen. If an alarm
point asserts while you are using a front-panel screen, the message area
notification reads:
ALARM EVENT
. If a trip event occurs while you are using a
front-panel screen, the message area notification reads
RELAY EVENT
. When
you repeatedly press
{ESC}
(as if returning to the
MAIN MENU
) during this
warning or trip alert situation, the relay displays the corresponding full-screen
automatic message concerning the warning or trip in place of the
MAIN MENU
.
If the front-panel display is at the
MAIN MENU
and a status warning occurs, the
full-screen warning replaces the
MAIN MENU
. After you view the warning,
alarm, or trip screen, pressing
{ESC}
returns the LCD to the
MAIN MENU
.
Figure 5.42
Sample Status Warning in the LCD Message Area
For a status failure, the relay immediately displays the full-screen status alert
regardless of the present front-panel operating state. The relay displays no
further LCD screens until the status failure clears. Should an unlikely status
failure event occur, contact your local Technical Service Center or an SEL
factory representative (see
Factory Assistance on page U.6.45
).
03/15/01 GROUP 1
00:00:05.387
EVENT: BCG T
LOCATION: 48.47
FREQ: 60.00
SHOT: 1P=0 3P=1
BK1 OPEN
BK2 CLOSED
EVENT SUMMARY 10002
RELAY STATUS
SEL-421-R101-V0-
Z001001-D20010315
S/N=0001001234
RELAY ENABLED
TEMPERATURE WARNING
*Circuit BK1 SF6 Gas
ALARM POINTS
Press to acknldge
1 Closed (OK to TIE)
0 Open (No TIE)
BUS TIE INTERLOCK
1
0
RELAY STATUS WARNING
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...