![Sel 421 Скачать руководство пользователя страница 237](http://html.mh-extra.com/html/sel/421/421_instruction-manual_1236410237.webp)
U.5.19
Date Code 20090715
User’s Guide
SEL-421 Relay
Front-Panel Operations
Front-Panel Menus and Screens
You can view summary event reports from the relay front-panel display by
selecting
EVENTS
from the
MAIN MENU
shows sample
EVENT
SUMMARY
screens for a phase-to-phase-to-ground fault. Use the
{Right Arrow}
and
{Left Arrow}
pushbuttons to show each of the summary screens for the
event. Event reports can also be viewed via a front-panel automatic message
(
Front-Panel Automatic Messages on page U.5.34
) or programmable front-
panel operator control pushbutton (
Front-Panel Operator Control Pushbuttons
The horizontal scroll bar indicates that you can view other event 10002
screens. Use the
{Up Arrow}
and
{Down Arrow}
pushbuttons to move among the
events in the summary buffer. Press
{ESC}
to return to the
MAIN MENU
.
Figure 5.21
EVENT SUMMARY Screens
SER
The Sequential Events Recorder records state changes of user-programmable
Relay Word bits. State changes are time-tagged for future analysis of relay
operations during an event. See
SER (Sequential Events Recorder) on
for more information on SER events. To view SER events from
the front panel, select
EVENTS
from the
MAIN MENU
and
SER Events
from the
Events Menu
as shown in
. SER events are also viewable using
programmable front-panel operator-control pushbuttons; see
.
illustrates the
SER Events
display screen. Data reported in this
screen for each event are the SER number, SER Point Alias Name, Asserted or
Deasserted state, and the Date and Time of the event. When in the
SER Events
screen, three SER records are displayed. Using the navigation pushbuttons,
the most recent 200 SER events are viewable on the front-panel display. The
topmost event is the most recent event and the bottommost event is the oldest.
The upper right of the screen displays the number of the SER events currently
being viewed. If a new event occurs while viewing the SER events, the display
does not update with the new event automatically. To include the new SER
event in the display, exit the SER screen by pressing
{ESC}
and re-enter the
SER
Events
screen by pressing
{ENT}
with the
SER Events
selection highlighted.
This rebuilds the
SER Events
display and contains the latest SER events
triggered.
Figure 5.22
SER Events Screen
If no SER events are available,
is displayed.
03/15/2001 GROUP 1
00:00:05.387
EVENT: BCG T
LOCATION: 48.47
FREQ: 60.00
SHOT: 1P=0 3P=1
BK1 OPEN
BK2 CLOSED
EVENT SUMMARY 10002
TARGETS:
COMM
ZONE 2
PHASE B
PHASE C
GROUND
50
EVENT SUMMARY 10002
FAULT QUANTITIES
(kV/A)
VA = 131 0.7˚
VB = 113 -123.4˚
VC = 113 124.7˚
IA = 200 -0.5˚
IB = 2478 172.3˚
IC = 2480 6.7˚
IG = 212 -11.3˚
EVENT SUMMARY 10002
Local
Disabled
02/16/06 11:11:01.993
Local
Enabled
02/16/06 10:11:19.090
IN101
Asserted
02/16/06 03:22:01.988
SER Events 001-003
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...