U.4.33
Date Code 20090715
User’s Guide
SEL-421 Relay
Basic Relay Operations
Examining Metering Quantities
Examining Metering Quantities
The SEL-421 features high-accuracy power system metering. You can view
fundamental and rms quantities by using a communications terminal,
AC
SEL
ERATOR
QuickSet, or the front panel. For more information on
SEL-421 metering, see
View Metering:
Terminal
The procedure in the following steps shows how to use a terminal or terminal
emulation computer program to view power system metering. In this example,
you connect specific voltages and currents for a 5 A, 60 Hz relay. Scale these
quantities appropriately for your particular relay. For more information on
testing the relay and making test connections, see
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page U.4.5
).
In addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords: Terminal on page U.4.9
to change the
default access level passwords).
Step 1. Prepare to control the relay at Access Level 2.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
c. Type the
2AC <Enter>
command.
d. Type the correct password to go to Access Level 2.
You will see the Access Level 2 =>> prompt.
Step 2. Set the relay to a nominal operation mode.
a. Use a terminal to perform the initial global settings
relay setup in
Making Settings Changes: Initial Global
b. Set the relay for 60-Hz operation, ABC phase rotation.
Step 3. Set the relay for a basic voltage and current configuration (see
). Use the terminal to set global settings ESS := 1.
a. Type
SET G ESS
TERSE <Enter>
.
b. Type
1 <Enter>
if the ESS setting is not 1.
c. Type
END <Enter>
to finish this settings session.
d. Answer
Y <Enter>
to the save settings prompt.
=>>
SET G ESS TERSE <Enter>
Global
Current and Voltage Source Selection
Current and Voltage Source Selection (Y,N,1,2,3,4) ESS :
=
N ?
1 <Enter>
Line Current Source (IW,COMB) LINEI :
=
IW ?
END <Enter>
Save settings (Y,N) ?
Y <Enter>
Saving Settings, Please Wait...........
Settings Saved
=>>
Figure 4.23
Setting ESS: Terminal
NOTE:
If the relay is in service,
disable any output circuits (such as
trip and close) to avoid an
unintended relay operation caused
by test signals.
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...