U.4.37
Date Code 20090715
User’s Guide
SEL-421 Relay
Basic Relay Operations
Examining Metering Quantities
=>>
MET <Enter>
Relay 1 Date: 02/26/2004 Time: 01:35:05.221
Station A Serial Number: 0000000000
Phase Currents
IA IB IC
I MAG (A) 398.882 399.041 398.784
I ANG (DEG) -1.18 -120.97 119.21
Phase Voltages Phase-Phase Voltages
VA VB VC VAB VBC VCA
V MAG (kV) 133.994 133.986 133.953 231.903 231.815 232.450
V ANG (DEG) -0.17 -120.02 120.18 29.91 -89.92 150.01
Sequence Currents (A) Sequence Voltages (kV)
I1 3I2 3I0 V1 3V2 3V0
MAG 398.901 2.159 2.588 133.977 0.692 0.713
ANG (DEG) -0.98 -62.68 -115.80 0.00 -53.25 -120.79
A B C 3P
P (MW) 53.44 53.46 53.41 160.31
Q (MVAR) 0.95 0.89 0.91 2.75
S (MVA) 53.45 53.47 53.42 160.33
POWER FACTOR 1.00 1.00 1.00 1.00
LAG LAG LAG LAG
FREQ (Hz) 60.00 VDC1(V) 125.00 VDC2(V) 48.00
=>>
Figure 4.27
Terminal Screen MET Metering Quantities
View Metering: Terminal on page U.4.33
fundamental line quantities. Other variants of the
MET
command give
different relay metering quantities. For example, you can see the line rms
(harmonics-included) quantities by issuing the
MET RMS
command. See
for more information on
the
MET
command.
View Metering:
AC
SEL
ERATOR
QuickSet
Use the procedures in the following steps to examine the SEL-421 metering
with the
AC
SEL
ERATOR
QuickSet HMI.
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page U.4.5
).
In addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords: Terminal on page U.4.9
to change the
default access level passwords). You should also be familiar with
AC
SEL
ERATOR
QuickSet (see
Step 1. Configure the communications port.
a. Start
AC
SEL
ERATOR
QuickSet.
b. On the top toolbar, open the
Communication
menu,
and then click
Port Parameters
.
You will see the
Port Parameters
dialog box similar to
.
c. Select the
Data Speed
,
Data Bits
,
Stop Bits
,
Parity
,
and
RTS/CTS
that match the relay settings. The
defaults are
9600
,
8
,
1
,
None
,
Off
, respectively.
d. Click
OK
to update the
AC
SEL
ERATOR
QuickSet
communications parameters.
e. Confirm that the
Communications Status
bar at the
bottom of the
AC
SEL
ERATOR
QuickSet window says
Connected
.
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...