U.4.69
Date Code 20090715
User’s Guide
SEL-421 Relay
Basic Relay Operations
Operating the Relay Inputs and Outputs
Figure 4.59
Control Input Pickup Level Settings in
AC
SEL
ERATOR
Quickset
SEL-5030 Software
Step 7. Set the control input IN101 pickup threshold.
For this example, a 125 Vdc station battery is providing the
control voltage. Referring to
appropriate pickup voltage settings is 100 Vdc. Click the
mouse cursor (or press
<Tab>
) to highlight
IN101P
Main
Board Input 101 Assertion Level
.
a. Delete the present setting by pressing
<Delete>
.
b. Type
100
, and then click or
<Tab>
to another value.
The relay checks the new value and enters the value in
the
AC
SEL
ERATOR
QuickSet database.
Figure 4.60
Control Input Pickup and Dropout Delay Settings in
AC
SEL
ERATOR
QuickSet
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...