U.6.7
Date Code 20090715
User’s Guide
SEL-421 Relay
Testing and Troubleshooting
Testing Features and Tools
Figure 6.1
Low-Level Test Interface
Main Board Processing Module Tests
Use signals from the SEL-4000 Low-Level Relay Test System to test the relay
processing module. Apply appropriate signals to the low-level test interface
J20 from the SEL-4000 Relay Test System (see
). These signals
simulate power system conditions, taking into account PT ratio and CT ratio
scaling. Use relay metering to determine whether the applied test voltages and
currents produce correct relay operating quantities.
The UUT Database entries for the SEL-421 in the SEL-5401 Relay Test
System Software are shown in
and
.
U.S. Patent 5,479,315.
Input Module Output (J3): 66.6 mV At Nominal Current (1 A or 5 A).
SEL-421 Relay
Low-Level Test Interface
446 mV at Nominal Voltage (67 V
LN
).
Processing Module Input (J20): 6.6 Vp-p Maximum.
Table 6.4
UUT Database Entries for SEL-5401 Relay Test System Software—
5 A Relay
Label
Scale Factor
Unit
1
IAW
75
A
2
IBW
75
A
3
ICW
75
A
4
IAX
75
A
5
IBX
75
A
6
ICX
75
A
7
VAY
150
V
8
VBY
150
V
9
VCY
150
V
10
VAZ
150
V
11
VBZ
150
V
12
VCZ
150
V
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...