Close the circuit breakers using Relay Word bits BK1CLS and BK2CLS for
Circuit Breaker 1 and Circuit Breaker 2, respectively.
Assigning Control Outputs for Tripping and Closing
The procedure in the following steps shows a method for setting the relay to
operate the trip bus and the close bus at a typical substation. Relay factory
defaults assign control outputs OUT101 and OUT102 to the trip bus and
OUT103 to the close bus for a three-pole tripping circuit breaker. This
procedure assigns an additional close output at OUT106.
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page U.4.5
).
In addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords: Terminal on page U.4.9
to change the
default access level passwords). You should also be familiar with
AC
SEL
ERATOR
QuickSet (see
).
Step 1. Configure the communications port.
a. Start
AC
SEL
ERATOR
QuickSet.
b. On the top toolbar, open the
Communication
menu,
and then click
Port Parameters
.
You will see the
Port Parameters
dialog box similar to
.
c. Select the
Data Speed
,
Data Bits
,
Stop Bits
,
Parity
,
and
RTS/CTS
that match the relay settings. The
defaults are
9600
,
8
,
1
,
None
,
Off
, respectively.
d. Click
OK
to update the
AC
SEL
ERATOR
QuickSet
communications parameters.
e. Confirm that the
Communications Status
bar at the
bottom of the
AC
SEL
ERATOR
QuickSet window says
Connected
.
Step 2. Confirm the correct
AC
SEL
ERATOR
QuickSet passwords.
a. Reopen the
Communication
menu and click
Port
Parameters
.
b. Enter your Access Level 1 password in the
Level One
Password
text box, and your Access Level 2 password
in the
Level Two Password
text box.
c. Click
OK
to accept changes and close the dialog box.
Step 3. Click
Settings > Read
.
The relay sends all configuration and settings data to
AC
SEL
ERATOR
QuickSet.
Step 4. Access the
Main Board
output settings.
a. Expand the
Outputs
branch of the
Settings
tree view.
b. Click
Main Board
(see
).
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...