U.6.31
Date Code 20090715
User’s Guide
SEL-421 Relay
Testing and Troubleshooting
Checking Relay Operation
Figure 6.23
Breaker 1 Breaker Monitor Settings:
AC
SEL
ERATOR
QuickSet
Step 2. Set test values in the relay.
a. Expand the
Group 1
settings as shown in
and select the
Line Configuration
button.
You will see the
Line Configuration
dialog box of
b. Confirm the default settings of
Z1MAG
at
7.80
and
Z1ANG
at
84.00
.
c. Click the
+
mark next to the
Relay Configuration
branch to expand that
Settings
branch.
d. Select the
Directional
button.
You will see the
Directional
dialog box similar to
e. Confirm the following settings:
E32
is
AUTO
,
ORDER
is
Q
,
50FP
is
0.60
,
50RP
is
0.40
,
Z2F
is
3.90
,
Z2R
is
4.00
,
a2
is
0.10
, and
k2
is
0.2
.
The dialog box is dim since there are no settings to
change.
The relay calculates these numeric settings
automatically because
E32
is set to
AUTO
.
f.
If you need to change these settings, set
E32
to
Y
.
shows the calculations.
Ground Directional Element on page R.1.27
for
details on these relay calculations.
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...