U.6.30
SEL-421 Relay
User’s Guide
Date Code 20090715
Testing and Troubleshooting
Checking Relay Operation
Checking the Negative-Sequence Directional Element (Phase Faults)
NOTE:
As you perform this test,
other protection elements can assert.
This causes the relay to assert other
targets and possibly close control
outputs. Be sure to isolate the relay
from the power system to avoid
unexpected system effects.
This test confirms operation of the F32Q and the R32Q negative-sequence
directional elements. This test procedure is for a 5 A relay; scale values
appropriately for a 1 A relay.
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page U.4.5
).
In addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords on page U.4.6
to change the default access
level passwords and enter higher relay access levels). You should be familiar
with
AC
SEL
ERATOR
QuickSet (see
Step 1. Configure the relay.
a. Open
AC
SEL
ERATOR
QuickSet and read the present
configuration in the SEL-421.
b. Click
Settings > Read
.
The relay sends all settings and configuration data to
AC
SEL
ERATOR
QuickSet.
c. Expand the
Group 1
settings and click the
Relay
Configuration
branch of the
Settings
tree view as
d. Disable supervisory elements.
Confirm that
ELOP
is set to
N
.
e. In a similar sequence, click on the + button to expand
the
Relay Configuration
tree view, click on
Load
Encroachment
, and confirm that
ELOAD
is set to
N
.
Figure 6.22
Group 1 Relay Configuration Settings:
AC
SEL
ERATOR
QuickSet
f.
Defeat the pole-open logic.
g. Click the
+
button next to
Breaker Monitor
to expand
the
Breaker Monitor
branch of the
Settings
tree view
(see
).
h. Click
Breaker 1
.
You will see the
Breaker 1
dialog box similar to
i.
Enter
1
in the text boxes for
52AA1 A-Phase N/O
Contact Input -BK1
,
52AB1 B-Phase N/O Contact
Input -BK1
, and
52AC1 C-Phase N/O Contact
Input -BK1
.
appear if Breaker
Monitor setting BK1TYP := 1.
j.
If BK1TYP := 3, enter
1
in the
52AA1 N/O Contact
Input -BK1
text box (the other circuit breaker input
boxes are dimmed.)
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...