U.4.15
Date Code 20090715
User’s Guide
SEL-421 Relay
Basic Relay Operations
Making Simple Settings Changes
Note that some settings classes have only one instance and you do not specify
the instance designator when accessing these classes. An example is the
Global settings class. You can view or modify Global settings with a
communications terminal by entering
SET G
as shown in the ASCII
Command column of
. The relay presents the Global settings
categories at the
SET G
command; no instance numbers follow
SET G
.
Table 4.5
Settings Classes and Instances
Class
Description
Instance
Description
ASCII
Command
Access
Level
Global
Relay-wide applications
settings
Global
SET G
P, A, O, 2
Group
Individual scheme settings
Group 1
•
•
•
Group 6
Group 1 settings
•
•
•
Group 6 settings
SET 1, SET S 1
•
•
•
SET 6, SET S 6
P, 2
Breaker
Monitor
Circuit breaker monitoring
settings
Breaker
Monitor
SET M
P, 2
Port
Communications port settings
PORT F
Front-panel port
SET P F
P, A, O, 2
PORT 1
•
•
•
PORT 3
PORT 1
settings
•
•
•
PORT 3
settings
SET P 1
•
•
•
SET P 3
PORT 5
Communications card
settings
SET P 5
Report
Event report and SER
a
settings
a
SER is the Sequential Events Recorder; see
SER (Sequential Events Recorder) on page A.3.34
Report
SET R
P, A, O, 2
Front Panel
Front-panel HMI settings
Front Panel
SET F
P, A, O, 2
Protection
SEL
OGIC®
control
equations
Protection-related SEL
OGIC
control equations
Group 1
•
•
•
Group 6
Group 1 protection
SEL
OGIC
control equations
•
•
•
Group 6 protection
SEL
OGIC
control equations
SET L 1
•
•
•
SET L 6
P, 2
Automation
SEL
OGIC
control
equations
Automation-related SEL
OGIC
control equations
Block 1
b
•
•
•
Block 10
b
The SEL-421-1 and SEL-421-2 have only one block of automation SEL
OGIC
control equations.
Block 1 automation
SEL
OGIC
control equations
•
•
•
Block 10 automation
SEL
OGIC
control equations
SET A 1
•
•
•
SET A 10
A, 2
DNP
Direct Network Protocol data
remapping
DNP
SET D
P, A, O, 2
Output
SEL
OGIC
control
equations
Relay control output
settings and M
IRRORED
B
ITS
communication transmit
equations
Output
SET O
O, 2
Alias
Set aliases
Analog
or digital
quantities
SET T
P, A, O, 2
Содержание 421
Страница 8: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 22: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 42: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 62: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 116: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 262: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 308: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...