95
07-09
DC braking time at stop
Factory setting
0.0s
Setting range 0.0s
~
100.0s
Starting frequency of DC braking at stop: When the running frequency is reduced to this frequency during
deceleration to stop, the DC braking process starts.
Waiting time for DC braking at stop: After the running frequency is reduced to the initial frequency of DC braking
at stop, the inverter will stop output for a period of time before starting the DC braking process. It is used to
prevent overcurrent and other faults that may be caused by starting DC braking at a higher speed.
DC braking current at stop: refers to the output current Output current during DC braking, as a percentage of the
motor rated current. The larger the value, the stronger the braking, but the greater the heat generated by the
motor and inverter.
DC braking time at stop: The time the DC braking amount is maintained. This value is 0, the DC braking process
is canceled. The DC braking process during shutdown is shown in the schematic diagram in Figure 5-12.
Output frequency Hz
Starting DC braking
frequency at stop
Run command
DC braking waiting
time at stop
DC braking time at stop
Time
Time
DC braking at stop
Effective value of
output voltage
Figure 5-12 Schematic diagram of DC braking at shutdown
07-10
Brake usage
Factory setting
80%
Setting range 0%
~
100%
It is only valid for the inverter with built-in braking unit.
The higher the braking usage rate, the stronger the braking effect, but the voltage fluctuation of the inverter bus
voltage during braking is large.
07-11
Acceleration and deceleration mode
Factory setting
0
Setting range
0
Linear acceleration / deceleration
1
S curve acceleration / deceleration A
2
S curve acceleration / deceleration B
Select the frequency change method of the inverter during start and stop.
0: linear acceleration and deceleration
The output frequency increases or decreases in a straight line. 4 kinds of acceleration/deceleration time can be
selected through multi-function digital input terminals (04-00
~
04-04).
1: S curve acceleration and deceleration A
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...