69
01-02
Motor rated power
Factory setting
Type setting
Setting range 0.1kW
~
1000.0kW
01-03
Motor rated frequency
Factory setting
Type setting
Setting range 0.01Hz
~
max frequency
01-04
Motor rated rotation speed
Factory setting
Type setting
Setting range 1rpm
~
65535rpm
01-05
Motor rated voltage
Factory setting
Type setting
Setting range 1V
~
2000V
01-06
Motor rated current
Factory setting
Type setting
Setting range
0.01A
~
655.35A(Inverter power <=55kW)
0.1A
~
6553.5A(Inverter power >55kW)
Note: The above are the motor nameplate parameters, regardless of V/f control or vector control, the relevant
parameters need to be set accurately according to the motor nameplate.
In order to obtain better V/f or vector control performance, motor parameter self-learning is required. Accurate
parameter self-learning comes from the correct input of motor nameplate parameters.
01-12
Motor type selection
Factory setting
2
Setting range
2
Permanent magnet synchronous motor
01-16
Stator resistance of synchronous motor
Factory setting
Type setting
Setting range
0.001Ω
~
65.535Ω(Inverter power<=55kW)
0.0001Ω
~
6.5535Ω(Inverter power >55kW)
01-17
D-axis inductance of synchronous motor
Factory setting
Type setting
Setting range
0.01mH
~
655.35mH(Inverter power <=55kW)
0.001mH
~
65.535mH(Inverter power >55kW)
01-18
Q axis inductance of synchronous motor
Factory setting
Type setting
Setting range
0.01mH
~
655.35mH(Inverter power <=55kW)
0.001mH
~
65.535mH(Inverter power >55kW)
01-20
Back-EMF coefficient of synchronous motor
Factory setting
Type setting
Setting range 0.1V~6553.5V
01-16~01-20 are the parameters of the synchronous motor. These parameters are generally not on the
nameplate of the motor, and need to be obtained through the inverter self-learning.
Among them, "synchronous motor on-load learning" can only obtain three parameters 01-16~01-18, while
"synchronous motor no-load learning" can obtain these four parameters.
If the synchronous motor cannot be learned on site,you can enter the above corresponding parameter values
according to the parameters provided by the motor manufacturer.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...