106
When the terminal jog priority is effective, if the terminal jog command appears during the operation, the inverter
will switch to the terminal jog running state.
09-28
Frequency detection value(FDT2)
Factory setting
50.00Hz
Setting range 0.00Hz
~
Max frequency
09-29
Frequency detection hysteresis(FDT2)
Factory setting
5.0%
Setting range 0.0%
~
100.0%(FDT2 Level)
The frequency detection function is exactly the same as the function of FDT1. Please refer to the relevant
description of FDT1, namely the description of parameters 09-19 and 09-20.
09-30
Arbitrary arrival frequency detection value 1
Factory setting
50.00Hz
Setting range 0.00Hz
~
Max frequency
09-31
Arbitrary arrival frequency detection width 1
Factory setting
0.0%
Setting range 0.0%
~
100.0%(Max frequency )
09-32
Arbitrary arrival frequency detection value 2
Factory setting
50.00Hz
Setting range 0.00Hz
~
Max frequency
09-33
Arbitrary arrival frequency detection width 2
Factory setting
0.0%
Setting range 0.0%
~
100.0%(Max frequency )
When the output frequency is within the range of the positive and negative detection amplitude of any detected
frequency, the multi-function output terminal (function 26/27) outputs an ON signal.
S3100E provides two sets of arbitrary arrival frequency detection parameters, set frequency value and frequency
detection range respectively. Figure 5-21 is a schematic diagram of this function.
Running frequency Hz
Time
Arbitrary arrival frequency
Arbitrary arrival frequency
detection signal
Frequency detection width
Frequency detection width
MO1,RELAY,DFM(M)
OFF
ON
OFF
OFF
ON
Figure 5-21 Schematic diagram of arbitrary arrival frequency detection
09-34
Zero current detection level
Factory setting
5.0%
Setting range 0.0%
~
300.0% (100.0% corresponds to the rated current of the motor)
09-35
Zero current detection delay time
Factory setting
0.10s
Setting range 0.01s
~
600.00s
When the output current of the inverter is less than or equal to the zero current detection level and the duration
exceeds the zero current detection delay time, the multi-function output terminal (function 34) of the inverter
outputs an ON signal. Figure 5-22 is a schematic diagram of zero current detection.
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...