116
11-11
Fault automatic reset interval time
Factory setting
1.0s
Setting range 0.1s
~
100.0s
Waiting time from inverter fault alarm to automatic fault reset.
11-12
Input phase loss protection selection
Factory setting
1
Setting range
0
Disabled
1
Enabled
Choose whether to protect the input phase loss.
S3100E frequency converter 7.5kW, G type and above power, only have input phase loss protection function,
7.5kW, P type power and below power, no matter 11-12 is set to 0 or 1, there is no input phase loss protection
function.
11-13
Output phase loss protection selection
Factory setting
1
Setting range
0
Disabled
1
Enabled
Choose whether to protect the output phase loss.
11-14
First failure type
Factory setting
-
11-15
Second failure type
Factory setting
-
11-16
Third (latest) fault type
Factory setting
-
Record the last three fault types of the inverter,0 is no fault. For the cause and solution of the fault, please refer to
the relevant instructions in Chapter 6.
11-17
Frequency at the third failure
Frequency at latest failure
11-18
Current at the third fault
Current at latest fault
11-19
Bus voltage at the third fault
Bus voltage at the latest fault
11-20
Input terminal status at the
third fault
The state of the digital input terminal during the latest failure, the
order is:
BIT9 BIT8 BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
MI0
MI9
MI8
MI7
MI6
MI5
MI4
MI3
MI2
MI1
When the input terminal is ON, the corresponding secondary system
bit is 1, OFF is 0, and all MI status is converted to decimal number
display.
11-21
Output terminal status at the
third fault
The state of all output terminals during the latest fault, the order is
BIT4
BIT3
BIT2
BIT1
BIT0
MO2
MO1 REL2 REL1 DFM(P)
When the input terminal is ON, the corresponding secondary system
bit is 1, OFF is 0, and all MI status is converted to decimal number
display.
11-22
Inverter status at the third
fault
Reserved
11-23
Power-on time at the third
fault
The current power-on time when the latest fault occurred
Содержание S3100E Series
Страница 1: ...S3100Eseries inverter General vector control PM User manual User manual ...
Страница 23: ...19 Size 3 Unit mm S3100E 2T5 5G 2T7 5G S3100E 4T7 5G 11P 4T22G Size 4 Unit mm S3100E 4T22G 30P 4T37G 45P ...
Страница 24: ...20 Size 5 Unit mm S3100E 4T45G 55P 4T110G Size 6 Unit mm S3100E 4T110G 132P 4T160G 185P ...
Страница 25: ...21 Size 7 Unit mm S3100E 4T185G 200P 4T220G Size 8 Unit mm S3100E 4T220G 250P 4T315G ...
Страница 26: ...22 Size 9 Unit mm S3100E 4T315G 355P 4T400G 450P Size 10 Unit mm S3100E 4T450G 500P 4T500G ...